Installation manual
A Guide To IBM System x Power Distribution Units (PDU) - International
P a g e | 17 © IBM Corporation 2012
IBM Switched and Monitored PDUs
IBM Switched and Monitored PDUs collect power statistics and have the ability to control outlets remotely via the PDUs web
interface or IBM Active Energy Manager.
PDU
Option
Number
Phase
Voltage
Line Cord
(Derated)
Number /
Type of Outlet
Page
1U 12 C13
46M4004
1ph
220-240VAC
32A IEC 309 P+N+G
12 / C13
18
63A IEC 309 P+N+G
230-240VAC
32A AUS/NZ 3112
220VAC
30A KSC 8305
3ph Y
380-415VAC
32A (32A/ph) IEC 309 3P+N+G
1U 9 C19 / 3 C13
46M4002
1ph
220-240VAC
32A IEC 309 P+N+G
9 / C19
3 / C13
18
63A IEC 309 P+N+G
230-240VAC
32A AUS/NZ 3112
220VAC
30A KSC 8305
3ph Y
380-415VAC
32A (32A/ph) IEC 309 3P+N+G
0U 24 C13U
46M4119
1ph
220-240VAC
32A IEC 309 P+N+G
24 / C13
19
0U 12 C19/12 C13
46M4137
3ph Y
380-415VAC
32A (32A/ph) IEC 309 3P+N+G
12 / C19
12 / C13
21
Note: ph indicates phase (1 or 3), Δ indicates three phase delta, and Y Indicates three phase WYE
IBM Switched and Monitored (Managed) PDUs Gathered Statistics
PDU Input Statistics:
Input Voltage (V) - Present Value, Min, Max
Input Current (A) - Present Value, Min, Max
Power Factor (0.0 - 1.0) - Present Value, Min, Max
Input Frequency (Hz) - Present Value, Min, Max
Input Power (W) - Present Value, Min, Max
Cumulative Kilowatt Hours - Present Value, Min, Max
Individual Outlet Statistics:
Output Voltage (V) - Present Value, Min, Max
Output Current (A) - Present Value, Min, Max
Output Power Factor (0.0 - 1.0) - Present Value, Min, Max
Load Watts (W) - Present Value, Min, Max
Cumulative Kilowatt Hours - Present Value, Min, Max