Installation manual
A Guide To IBM System x Power Distribution Units (PDU) - International
P a g e | 11 © IBM Corporation 2012
IBM DPI Ultra Density Enterprise PDU
Input Line Cords
40K9611 – IBM DPI IEC-309 3P+N+G (4.3m) line cord
32A (32A / Phase) 380-415VAC Three Phase Wye
96A Total Circuit Capacity
40K9612 – IBM DPI IEC 309 P+N+G (4.3m) line cord
32A / 220-240VAC Single Phase
FC: 6504 = 71762NX + 40K9611
FC: 6502 = 71762NX + 40K9612
40K9613 – IBM DPI IEC 309 P+N+G (4.3m) line cord
63A / 220V-240VAC Single Phase
40K9617 – IBM DPI AS/NZS 3112 32A (4.3m) line cord
32A / 220VAC Single Phase
40K9618 – IBM DPI KSC 8305 30A (4.3m) line cord
30A / 230VAC Single Phase
FC: 6503 = 71762NX + 40K9613
FC: 6505 = 71762NX + 40K9617
FC: 6506 = 71762NX + 40K9618
Monitorable: No
Switched Outlets: No
Ground Screw: Yes – On Back Panel
See the Enterprise Deep PDU Mounting Options section on page 41 for
mounting option details.
Accessory Kit
(2) Vertical mounting brackets (for all rack cabinets)
(2) Horizontal mounting brackets
(1) 1U blank filler panel
Miscellaneous hardware kit (for attaching the mounting
brackets to the PDU and installing in a rack cabinet) and
cable straps
(1) Cable-management bracket (for vertical installations)
(2) Adjustable mounting rails (for horizontal mounting in all
rack cabinet)
For an overview of IBM Basic PDUs, go back to the beginning of this section IBM Basic PDUs on page 6.
1
2
3
4
5
6
7
8
9
A
B
C
D E
F
1
2
12
11
10
71762NX
Front Panel
Back Panel
Outlet
Number
Internal Circuit Layout
Outlet Type
Outlet
Amperage
Breaker
Amperage
Color Indicates Outlet Grouping Per Phase
On Three Phase Model
C13
C13
C13
C19
C19
C19
C19
C19
C19
C19
C19
C19
20A
20A
20A
10A
10A
10A
16A
16A
16A
16A
16A
16A
16A
16A
16A
20A
20A
20A
20A
20A
20A
3
4
5
6
7
8
9
10
11
12
1
2
10A Max
Group
Amperage