User's Manual
IS-204, IS-205, IS-206
InteliSocket
™
Ibis Networks
·
828 Fort Street Mall Suite 600
·
Honolulu, HI 96813
·
www.ibisnetworks.com 2
05/28/15
PART NUMBERING
Type Voltage Current Connector
IS-204 120 20 5-20P
IS-205 240 15 6-15P
IS-206 240 20 6-20P
COMPLIANCE
Agency File
UL916 – Energy Management Equipment E470522
ZigBee Profile (Ibis Automation) 0x114B
FCC 2AECN200
ENVIRONMENTAL
Parameter Symbol Min Typ Max Units
Operating Temperature T
O
0 25 40 C
Storage Temperature T
S
-40 100 C
Relative Humidity RH 0 95 %
InteliSockets are for indoor use only.
PROTOCOL
InteliSockets use the Ibis custom ZigBee profile for commands, acknowledgements, and
reporting of data. Refer to the V2 Protocol documentation for details.
DATA
InteliSockets report data typically every 15 seconds. Each report packet is comprised of socket
type, ZigBee channel, ZigBee hive (PANID), interval (seconds), voltage (RMS), frequency (Hz),
energy (watt-seconds), and power factor (fraction). From these data we can calculate
instantaneous power (watts) and current (amps).