Instruction Manual

Chapter 3 Wiring 3.1 Positioner Mode 1 (Standard Type)
99
2) PIO Pattern 1 ··················Solenoid Valve Type
0V (NPN Type)
24V DC (PNP Type)
Start Signal No.0
Start Signal No.2
Start Signal No.1
Reset
Pause
ERC3
A9
B9
A10
B10
A11
B11
A12
B12
A13
B13
ST0
ST1
ST2
RES
*STP
PE0
PE1
PE2
*ALM
24V DC (NPN Type)
0V (PNP Type)
Current Position No.0
Current Position No.1
Current Position No.2
Alarm
BR 2
RD 2
OR 2
YW 2
GN 2
BL 2
PL 2
GY 2
WT 2
BK
“*” in codes above shows the signal of the active low. Processing occurs when an input signal
of the type is turned OFF. An output signal of the type is normally ON in the power-on status
and turned OFF at signal output.
Ɣ Use the attached cable for the I/O connection.
Model : CB-ERC3P-PWBIOƑƑƑ (ƑƑƑ indicates the cable length L. Example. 020 2m)
L
B A
10
13
12
11
2
3
9
8
7
6
5
4
1
Display of Mode Code
Pin No.
Wire
Color
Signal
Abbreviation
Width Pin No.
Wire
Color
Signal
Abbreviation
Width
A1 Drain FG
AWG22
(0.3mm
2
)
B1 BR CP
A2 B2 RD CP_GND
AWG22
(0.3mm
2
)
A3 RD 1 BK B3 OR MP
A4 OR 1 EMG
AWG28
(0.08mm
2
)
B4 YW MP_GND
AWG19
(0.75mm
2
)
A5 B5 GN
A6 B6 BR 1
A7 BL B7 PL
A8 GY B8 WT
A9 BR 2 ST0 B9 RD 2 ST1
A10 OR 2 ST2 B10 YW 2
A11 GN 2 RES B11 BL 2 *STP
A12 PL 2 PE0 B12 GY 2 PE1
A13 WT 2 PE2
AWG28
(0.08mm
2
)
B13 BK *ALM
AWG28
(0.08mm
2
)
(Note) Wire color No.1 is colored with short-dotted line and No.2 with long-dotted line.