Owner's manual

Part 2 Programs
Chapter 3 Explanation of Commands
118
Part 2 Programs
z OUTB (Write output, flag as BCD)
Command, declaration
Extension condition
(LD, A, O, AB, OB)
Input condition
(I/O, flag)
Command,
declaration
Operand 1 Operand 2
Output
(Output, flag)
Optional Optional OUTB Output, flag BCD digits CC
[Function] Write the value in variable 99 to the output ports or flags from the one specified in operand 1
for the number of digits specified in operand 2 as a BCD.
85
Variable 99
307 306 305 304 303 302 301 300
Output port number
ON OFF OFF OFF OFF ON OFF ON
(Note 1) A maximum of eight digits (32 bits) can be output.
(Note 2) The number of output ports and flags that can be used is 4 x n (digits).
(Note 3) The write data format can be changed using a FMIO command (refer to the section on FMIO
command).
[Example 1] OUTB 300 2 Write the value in variable 99 to the output ports from
300 for two digits (until output port 307) as a BCD.
[Example 2] LET 1 300 Assign 300 to variable 1.
LET 2 2 Assign 2 to variable 2.
OUTB *1 *2 Write the value in variable 99 to the output ports from
the content of variable 1 (output port 300) for the
content of variable 2 (two digits) (until output port 307)
as a BCD.