User Manual

21
V. Trouble Shooting
AIR PROVING ERROR
The ICECON2 controller has
lost the Tachometer signal.
Check combustion blower
operation.
Check tachometer sensor
operation (see section
******).
Check ICECON2 fuses
FLAME ERROR
The ICECON2 controller has
lost the 24 VAC on terminal
J22.
Check gas supply
Check ignition module for
proper operation
Check all fail safes for
proper operation
Check valves, manual and
solenoid, for proper
operation
Check ICECON2 fuses
HIGH LIMIT ERROR
The ICECON2 controller has
received a temperature
reading above the factory set
value.
Check main blower and dampers
for proper operation.
Check discharge sensor for
correct attachment. Open
contacts on the Discharge
sensor terminals will cause
indication of a high limit
condition.
Check ICECON2 fuses
LOW LIMIT ERROR
The ICECON2 controller has
detected a temperature below
that set by the as the low
limit.
Check unit for proper
operation.
Check discharge sensor.
Continuity between the white
and black terminals will
return a –51 degree F signal.
Check ICECON2 fuses
VALVE ERROR
The ICECON2 controller has