Site Requirements 90DIB500R41SR_FCC02 99.1 19
DIB-500 R4.1 Requirements concerning the operation room
Infrastructure
4 Requirements concerning the operation
room
This chapter describes the requirements for the service room that must always be met
to ensure proper operation of the product element as intended at all times.
4.1 Infrastructure
The following section describes the infrastructure requirements for the site/service
room.
4.1.1 General requirements
The following requirements must be met for being able to operate the product as
intended:
| The operation room must be self-contained to ensure that the system technology is
protected at all times (protection against animals, for example).
| Unimpeded access to all the service and supply rooms must be possible.
The required access width to the operation room depends on the dimensions and
the weight of the equipment rack, refer to section 4.1.3.1 on page 20, and on the
condition of the operation room.
However, a minimum access width of 800 mm is required. An access width of at
least 1,200 mm is recommended for transports involving an angle.
Access doors must feature an inside width of at least 800 mm.
Opening heights (door, window and elevator openings, etc.) are dependent on
the free area in front of the access opening and, if necessary, the depth of the
respective elevator.
To position the equipment rack using lifting or transport equipment (e.g. lift
trucks), appropriate openings may have to be provided in the operation room.
| Service and access rooms must be suitable for the expert installation of any
required feed lines.
Scope of the site requirements
When the building or the operation room is/are modified, the equipment rack site must
still meet the site requirements.