Submittal

Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
04/14 4 Page _____ of _____
Single Phase Soft Starters
The manufacturer works continually to improve its products. As a result, the design and speci cations of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signi es that the equipment is acceptable under the
provisions of the job speci cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Physical Characteristics
Operating Characteristics
Software Characteristics
SureStart Model
Single Phase
SS0B12-20 SS1B08-16 SS1B16-32
Software Fault Delay, seconds 300 300 300
Initial Power on Delay, seconds, 60 Hz [50Hz] 1 [2] 1 [2] 1 [2]
Power Loss Reset, milliseconds 100 100 100
Contactor Chatter Protection Yes Yes Yes
Motor Reversal Protection Yes Yes Yes
Software Optimization Auto tune
10/01/13
SureStart Model
Single Phase
SS0B12-20 SS1B08-16 SS1B16-32
Storage Temperature,
o
F [
o
C] -40 [-40] to 185 [85]
Case Material ABS Flameproof UL-94 V0
IP Rating IP207
Line Conductor, AWG 14 - 6 14 - 6 14 - 6
Line Conductor Strip Length, in. [mm] 0.47 [12] 0.47 [12] 0.47 [12]
Minimum Line Conductor Length, in. [mm]
15.7 [400] 15.7 [400] 15.7 [400]
Line Terminal Tightening Torque, in-lbs [N-m] 11.5 [1.3] 11.5 [1.3] 11.5 [1.3]
Start Winding & Compressor Common, AWG 16-12 16-12 16-12
03/06/14
SureStart Model
Single Phase
SS0B12-20 SS1B08-16 SS1B16-32
Rated Voltage, VAC 115 208-230 208-230
Rated Phase 1 1 1
Rated Frequency, Hz 60 50/60 50/60
Maximum Load Current, Amps 20 16 32
Maximum Starting Current, Amps
35 35 65
Control input, VAC Auto-Start at Power Up
Number of Starts/Hour (Evenly Distributed) 15 15 15
Short Circuit Current Rating (SCCR), kA 5 5 5
Shutdown on Low Voltage 98 175 175
Minimum Startup Voltage 103 180 180
Maximum High Voltage 126 253 253
Operating Ambient,
o
F [
o
C] -4 [-20] to 140 [60]
Life Expectancy (At Maximum Rated Load) Minimum 100,000 Operations
03/06/14