ELECTRO-WELLS™
Fuel Smart HydroStat
installed with Electro-Well™
When installed with the Hydrolevel Electro-Well™, Fuel
Smart HydroStat will provide both temperature and low
water cut-off functionality. If the control was supplied by
the boiler manufacturer, it was installed with an
Electro-Well™. The Electro-Well™ is available sepa-
rately for field installations.
Electro-Well™ Models
IMPORTANT:
For proper opera-
tion of the low
water cut-off func-
tion, there must
be a minimum of
½" clearance
between the cop-
per well tube and
any surface within
the boiler.
MAINTENANCE
Remove the Electro-Well™ from the heating system every five years and clean any scale or sediment deposits from all parts that