Install Instructions
2
INSTALLING THE CONTROL
5 Remove the knockout and replace it with the
plastic bushing.
NOTE: For line voltage applications replace the
knockout with proper conduit in accordance with
all applicable codes and ordinances.
1 Locate the immersion well in the tank that is
designed for the temperature control.
2 Hold the AcuTemp control onto the well and
tighten the screw at the base of the control.
3 Slide the sensor into the well. NOTE: two
sensor diameters (3/8" & 1/4") are available to
accommodate different well sizes.
WARNING: The sensor must be fully inserted and fit snugly in the well for proper operation.
If a smaller sensor is used or the sensor is not fully inserted overheating and scalding could result.
4 Trim the sensor wire to the required length (if
needed). Plug the sensor wire into the sensor
input. The terminals are not polarity sensitive.
NOTE: Be sure the wires are fully inserted into the
sensor input.
3A Sensor and Well
(remote mounted control)
1. Insert the sensor all the way into the well.
2. Install the rubber well cap onto the sensor wire
and slide to cover the end of the well