Product Overview

15
Model VXTC
Programmable Feed Delay Settings (0 to 10 Min)
Prevents over-filling by allowing time for condensate to return to boiler
before initiating feed cycle. A “NO DELAY” delay setting is available for
process steam applications.
Programmable Feed Amount Settings (LWCO to LWCO+120 Sec)
Includes one setting to raise the water level to the boiler control and five
additional settings to raise the water level above the boiler control.
LED Status Indicator
Displays current mode of operation. Also provides timer for convenient
set-up of programmable feed amount setting.
Manual Feed Button
Allows for manual feeds with the touch of a button.
Lock-Out Flood Protection
Locks out after sustained 10 minute feed cycle to prevent flooding.
Water Meter
Heavy duty meter tracks make-up water added to system.
Fittings
Includes fittings for easy attachment to 3/4" water line.
MODEL VOLTAGE DESCRIPTION/OPERATION
VXTC 120 VAC Designed to operate with all major low water cut-offs and pump controllers.
Upon a low water signal from the boiler control, the VXTC delays (from 0 to 10
minutes) to allow condensate to return to the system. If make-up water is
required following the delay period, the VXTC initiates a feed cycle. The VXTC
can be set to feed to the level of the boiler control or to varying levels above. The
heavy-duty water meter tracks all water fed into the system. The VXTC includes
water feeder, strainer, flow restrictor and water meter with 3/4" NPT fittings.
VXTC-WF 120 VAC Water Feeder as above without water meter. Includes water feeder, strainer and
flow restrictor.
WM-1 n/a Water Meter as described above without water feeder. Includes water meter and
3/4" NPT fittings.
S T E A M B O I L E R C O N T R O L S
Water Feeder Commercial/Industrial
Specifications VXTC
Max. Feed Water Temperature 100° F
Flow Rate (@ 40 PSI) 10 GPM
Electrical 120 VAC, 60 HZ
Fittings 3/4" NPT