Install Instructions
PROBES
Test Pressure: 1000 PSI, All Models
THE PROBE MAKES THE DIFFERENCE
The probe used in all Hydrolevel controls offers you
distinctive advantages. Unlike float devices, there
are no moving parts to wear stick, or “hang-up” the
in harsh boiler environment .
A stuck or “hung-up” float can cause dangerous
low water conditions. And if suddenly released, a
float can feed cold water into overheated tubes or
plates and cause explosive results.
The Hydrolevel control has no float bowl so sedi-
ment cannot collect. The reliable solid state circuitry
and low maintenance probe are designed to provide
years of troublefree operation.
MAXIMUM PRESSURE: 15 PSI
INPUT VOLTAGE: 120 VAC, 60 HZ
SWITCH RATINGS: 5.8 FLA, 34.8 LRA
SWITCH CONTACTS: SPDT
ALARM CIRCUIT: 125 VA @ 120 VAC
Pilot Duty
EL1214 – STANDARD MODEL – 3/4" NPT
For 1/2", order Model No. EL-1220
EL1214-P – 3/4" NPT
LIMITED MANUFACTURER’S WARRANTY
We warrant products manufactured by Hydrolevel
Company to be free from defects in material and
workmanship for a period of two years from the
date of manufacture or one year from the date of
installation, whichever occurs first. In the event of
any claim under this warranty or otherwise with
respect to our products which is made within such
period, we will, at our option, repair or replace such
products or refund the purchase price paid to us by
you for such products. In no event shall Hydrolevel
Company be liable for any other loss or damage,
whether direct, indirect, incidental or consequential.
This warranty is your EXCLUSIVE remedy and shall
be IN PLACE OF any other warranty or guarantee,
express or implied, including, without limitation, any
warranty of MERCHANTABILITY or fitness for a par-
ticular purpose. This warranty may not be assigned
or transferred and any unauthorized transfer or
assignment thereof shall be void and of no force or
effect.
2"
SQUARE
1
7
/8"
3
13
/16"
15
/16"
1"
3
/4" NPT
5
/16"
2"
SQUARE
1
7
/8"
4
9
/16"
1"
3
/4" NPT
5
/16"
1
11
/16"
EL1214-R
REMOTE PROBE
2
25
/32
3
7
/8
1
5
/8
1
1
/8
1
5
/8
2
3
/8
BOTTOM
5
9
/16
5
1
/2
1.00
BACK
1
1
/8
2
3
/8
1
5
/8
TOP
The VXT Water Feeder (available separate-
ly) can be installed with Hydrolevel or other
low water cut-offs to automatically replen-
ish boiler water in the event of a low water
condition. The VXT offers programmable
feed amount and feed delay settings.
These can easily be set to ensure the
proper feed amount and to provide ade-
quate time for condensate to return to the
boiler before starting a feed cycle. The
VXT Feeder’s Digital Feed Counter tracks
the amount of water added to the boiler
exposing system leaks, which can signifi-
cantly shorten the life of a cast iron boiler.
Additional features including a manual
feed button, underfeed and flood protec-
tion make the VXT an ideal choice for safe-
ty and convenience.
VXT WATER FEEDER
126 Bailey Road
North Haven, CT 06473
Phone: (203) 776-0473
FAX: (203) 764-1711
www.hydrolevel.com
051118