Install Instructions
WIRING TO CONTROL CENTER
For boilers equipped with a Honeywell R8285 Control Center or equivalent
WIRING TO AN AQUASTAT
For boilers equipped with a Honeywell Model L8148E or L8124E Aquastat
YGW
CR
Connect the WHITE wire to C and the RED wire to R
using the screw terminals on the control center.
Connect the GREEN wire to any suitable, unpainted
ground screw. Note: for operation of the control, the
green wire must be connected to a ground source
electrically common with boiler ground.
➀
Unplug the factory-wired quick connect from termi-
nal R and
➁
plug into YELLOW wire with male con-
nector.
➂
Plug YELLOW wire with female connector
into terminal R.
Connect the WHITE wire to TV and the RED wire to Z. Connect the
GREEN wire to the ground screw on the bottom of the aquastat or any
other suitable, unpainted ground screw. Note: for operation of the con-
trol, the green wire must be connected to a ground source electrically
common with boiler ground.
➀
Unplug the factory-wired quick con-
nect from terminal B1 and
➁
plug into
YELLOW wire with male connector.
➂
Plug YELLOW wire with female
connector into terminal B1.
UPON COMPLETION OF WIRING,
REPLACE COVER.
Step
➊
Step
➋
Step
➊
Step
➋