FLOW SPECIFICATIONS
Pipe Size
1" 1
1
4" 1
1
2" 2" 2
1
2" 3" 4" 5" 6"
Minimum
Adjustment
Flow
Increases
4.5 8.1 11.8 16.5 25 33 51 85* 120*
Flow
Decreases
2.2 6.8 7.6 9.3 19 22 38 75* 100*
Maximum
Adjustment
Flow
Increases
14.8 22.1 25.7 32.3 75 90* 110* 170* 240*
Flow
Decreases
13.8 20.1 23.7 30.5 72 85* 100* 155* 220*
*Calculated for various pipe sizes. Flow rates may vary ±10% from values above.
MODEL FS200 MODEL FS204
Enclosure: NEMA 1 – General Purpose NEMA 4 – Wet Locations
Control Chassis Material: 13 gauge galvanized steel Anodized cast aluminum
Control Cover Material: 16 gauge powder coated steel Powder coated cast aluminum
Maximum Fluid Temperature: 250°F (121°C) 250°F (121°C)
Minimum Fluid Temperature: 32°F (0°C) 32°F (0°C)
Contacts: SPDT switch 7.4 FLA, 44.4 LRA SPDT switch 7.4 FLA, 44.4 LRA
@120VAC Motor Duty @120VAC Motor Duty
Pilot Duty Rating: 125VA@120/240VAC 125VA@120/240VAC
Maximum Service Pressure: 160 psi 160 psi
Usage: 1" to 6" pipe sizes (see Flow Chart) 1" to 6" pipe sizes (see Flow Chart)
EPDM Seal for Superior Performance over Mechanical Bellows
Universal Design – Replaces Flow Switches by McDonnell Miller,
Penn, Taco, Potter, Watts and others
Single Pole Double Throw Switch for Operating Signal Devices,
Motors, Alarms, Metering Devices and Heating Units
Four Heavy Duty Stainless Steel Paddles
Two 7/8" Electrical Knock-Outs for 1/2" Conduit
For Use on 1" to 6" Diameter Pipe
1" NPT Pipe Connection
Model FS200