Technical Specifications

Zoning By Telestats
M
D
Telestats are used for zoning. ey are placed on your hydronic manifold and
control ow through each individual loop on a zone. Telestats can be paired
up to 4 loops per zone. When zoning by telestats, you must have a telestat on
every single loop of your manifold. You must have a minimum of 3 loops per
zone, as this will help prevent short cycling. You can achieve multiple zones
on one manifold. For Example: you can have a 9 POS manifold, and break
that into 3 zones, each with 3 loops per zone, with a telestat on each loop. is
scenario would require 3 thermostats, one for each zone. e ermostats
and Telestats will get wired to the control that comes with your panel.