Technical Specifications

e HS2T3ZPMP is a 2 Water Delivery Temperature, 3 Zone by Pumps Zone Panel. is
panel can be used with e HSPS120MPH, HSPS190MPH, HSPS150MPH-HTP, or the
HSBP6W-HS115-MPH integrator panels. is panel is desinged to be used when you
have two dierent emitter types that reqire two dierent water deliver temperatures. For
example, tubing in concrete should never go above 130° while baseboard usually requires
145°-160°. If you had both of these emitters, you would need a 2 Temp Panel. is panel
requires 3 thermostats, 1 for each zone.
Compatible Integrator Panels
•HSPS120MPH
•HSPS190MPH
•HSBP6W-HS115-MPH
•HSPS150MPH-HTP