User guide

ContaminationSensor CS1000 Analog Output (ANAOUT)
HYDAC Filtertechnik GmbH
en
Page 77 / 100
BeWa CS1000 3247149n en 2009-02-04.doc 2009-02-04
Fluid temperature (TEMP)
The current range 4.8 - 19.2 mA or voltage range 2.4 - 9.6 V is dependent on the
fluid temperature of from -25°C – +100°C (resolution: 1°C) or -13°F – 212°F
(resolution: 1°F)
Current I Temperature / error Voltage U
I < 4.00 mA Cable break U < 2.00 V
4.0 mA < I < 4.1 mA Device error, device not ready 2.00 V < U < 2.05 V
4.1 mA < I < 4.3 mA Not defined 2.05 V < U < 2.15 V
4.3 mA < I < 4.5 mA Flow error (flow insufficient) 2.15 V < U < 2.25 V
4.5 mA < I < 4.8 mA Not defined 2.25 V < U < 2.40 V
I = 4.8 mA -25 °C / -13 °F U = 2.40 V
... ... ...
I = 7.68 mA 0 °C / 32 °F U = 3.84 V
I = 8.26 mA +5 °C / 41 °F U = 4.13 V
I = 8.83 mA +10 °C / 50 °F U = 4.42 V
I = 9.41 mA +15 °C / 59 °F U = 4.70 V
I = 9.98 mA +20 °C / 68 °F U = 4.99 V
I = 10.56 mA +25 °C / 77 °F U = 5.28 V
I = 11.14 mA +30 °C / 86 °F U = 5.57 V
I = 11.71 mA +35 °C / 95 °F U = 5.86 V
I = 12.29 mA +40 °C / 104 °F U = 6.14 V
I = 12.86 mA +45 °C / 113 °F U = 6.43 V
I = 13.44 mA +50 °C / 122 °F U = 6.72 V
I = 14.02 mA +55 °C / 131 °F U = 7.01 V
I = 14.59 mA +60 °C / 140 °F U = 7.30 V
I = 15.17 mA +65 °C / 149 °F U = 7.58 V
I = 15.74 mA +70 °C / 158 °F U = 7.87 V
I = 16.32 mA +75 °C / 167 °F U = 8.16 V
I = 16.90 mA +80 °C / 176 °F U = 8.45 V
I = 17.47 mA +85 °C / 185 °F U = 8.74 V
I = 18.05 mA +90 °C / 194 °F U = 9.02 V
I = 18.62 mA +95 °C / 203 °F U = 9.31 V
I = 19.20 mA +100 °C / 212 °F U = 9.60 V
19.2 mA < I < 19.8 mA Not defined 9.60 V < U < 9.90 V
19.8 mA < I < 20 mA No measured value 9.90 V < U < 10 V