HDA.SAE – Analog signal SAE to the HDA 5500
The HDA.SAE signal consists of 6 values (START / SAE A / SAE B / SAE C / SAE
D / Status) which are output sequentially. Synchronization with the downstream
control unit is a prerequisite.
The signal output is as follows:
Time Measurement
category
Signal duration
in s
Current/Voltage
Start signal 0 -- 2 20 mA / 10 V
Pause 2 4 mA / 2 V
Signal 1 SAE A 2 Current/Voltage for signal
Pause 2 4 mA / 2 V
Signal 2 SAE B 2 Current/Voltage for signal
Pause 2 4 mA / 2 V
Signal 3 SAE C 2 Current/Voltage for signal
Pause 2 4 mA / 2 V
Signal 4 SAE D 2 Current/Voltage for signal
Pause 2 4 mA / 2 V
Signal 5 Status 2 Current/Voltage for signal
Pause 30 4 mA / 2 V