Product Manual

3.
Problem: Flames discharging from fuel door during reloading.
Troubleshooting
1.
Problem: Circulation blower runs constantly.
NOTE: Make sure the white button on the fan limit control is pulled out and in the “auto” position.
• Insufcient natural draft or an
obstruction in the ue system.
• See Troubleshooting Problems #6 and #9.
• Fire chamber lled to capacity with
unburned fuel.
• Do not attempt to overload the furnace.
Possible Causes:
• Opening the door has provided
additional oxygen which has ignited the
accumulated gases from partially spent
fuel.
Remedies:
Always open the door cautiously and allow the safety latch system to
perform its designed function, containing gases within the re chamber.
Possible Causes:
• Fan limit control is in “TEST” mode:
white button is pushed in.
Remedies:
• Pull white button out into the “AUTO” position.
• “OFF”setting on fan limit control is low. • Remove cover on fan limit control and check for the proper setting. The
point indicators should be set at 100°F “OFF” and 150°F “ON.” Do NOT
attempt to adjust the temperature indicators on the dial.
• Defective fan limit control. • Check by moving the “ON” and “OFF” point indicator to a temperature
position where blower should turn off. If the blower continues to run, replace
the fan limit control.
• Improper wiring. • Review wiring diagram. If unit is wired correctly, seek professional
assistance.
2.
Problem: Circulation blower vibrates during operation.
• Balance weights on squirrel cage have
become dislocated.
• You may attempt to adjust the weights yourself to obtain an acceptable
balance. If you are unsuccessful, contact your supplier.
• Dirt and debris on blower. After the unit is cold, inspect the blower housing and clean as needed.
Possible Causes:
• Set screw on squirrel cage is not tight.
Remedies:
• Check squirrel cage alignment and position so that it does not drag on the
housing during rotation, then tighten the screw sufciently to fasten the
squirrel cage securely to the shaft.
19