Corp. Network Router User Manual

DEFROST MENU (continued)
WITH THE CURSOR ON A CIRCUIT NUMBER, press the
ENT key to open that circuit submenu.
CIRCUIT #6 - REFR
Press the CLR key. Key in the applicable Lineup
name. Press ENT. Repeat for NAME, NUMBER/DAY,
DEFR LENGTH and 1ST DEFR HOUR:MINUTES.
Note: To key in name, press Shift Upper to use
the red (upper) letters and Shift Lower to use the
blue (lower) letters.
Three different types of defrost may be used:
Offtime
Gas
Electric
Using the key, toggle to the desired defrost
type. Press ENT.
The amperage number is used for electric
defrosts to turn off compressors and reduce over-
all amp draw.
Using the key, toggle between
E N A B L E D /
D I S A B L E D for defrost termination. Press E N T.
Note: the termination signal is provided by the
appropriate Auxiliary input (i.e., A
U X1 for CK T 1,
AU X 2 for CK T 2, …).
The remaining defrosts are listed. The control
panel spaces the number of defrosts evenly
across a 24 hour day. To customize the defrost
schedule, press the C L R k e y. Key in the applic-
able hour for defrost start. (Defrost times can be
entered on the quarter hour – :00, :15, :30 or
:45.) Press E N T. Press the C L R k e y. Key in
the applicable minute for defrost start. Press
E N T.
Press ESC to return to previous screen and to
return to V
IEW / SET ITEMS MENU.
Press ESC again to return to DEFROST MENU.
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.) 970307
P/N 374511B
Page 24
PROTOCOL
Hand Held Device
D E F ROST MENU
C I R C U I T S Y S T E M S TAT U S
5 0 0 N / A
6 0 0 N / A
7 0 0 N / A
8 0 0 N / A
PRESS ENT TO SET
CIRCUIT #6 - REFR
N A M E -
DEFR T Y P E - O F T I M
N U M B E R / DAY - 0 3
DEFR LENGTH - 1 5
1ST DEFR - 0 0 : 0 0
A M P E R AG E - 0 0
CIRCUIT #6 - REFR
DEFR T E R M - E N A B L E D
2ND DEFR - 0 8 : 1 5
3ND DEFR - 1 6 : 0 0
END OF DEFRO S T S