Corp. Network Router User Manual
CONFIG MENU (continued)
6- TEMPERATURE CONTROL
Press 6 on the Keypad to enter the Temperature
Control Submenu.
Note: Temperature Control is available on HAND
HELD DEVICE V2.40 or greater.
Press the number of the Temp Refr Circuit you
wish to view or use the and to move to the
appropriate entry and press ENT.
1-REFR CIRCUIT #1
This screen allows configuration for temperature
control of a given circuit.
Use the key to toggle between
E N A B L E D /
D I S A B L E D to activate the control function. Press
E N T.
SETPOINT will be the setting the control will try to
achieve for this circuit.
R
AT E is a number from 1 to 3 which allows the
algorithm to be adjusted for different evaporators.
Arate of 1 establishes a 30 second cycle rate for the
output; 2 establishes a 60 second cycle rate; and
3 establishes a 90 second cycle rate. You may need
to experiment with the rate adjustment in order to
achieve the optimum level of performance.
OUTPUT controls the relay used by the correspond-
ing Defrost Circuit.
Important – Verify the output number between
this temperature circuit and the connected
defrost circuit to ensure proper energizing and
de-energizing of solenoids. Make sure that in
the case of electric defrosts, you haven’t select-
ed the output that operates defrost heaters.
Press ESC to return to T
EMP CONTROL MENU.
Press ESC again to return to CONFIG MENU.
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.) 970307
P/N 374511B
Page 22
PROTOCOL
™
Hand Held Device
CONFIG MENU
1-SET THE CLOCK
2-SENSOR SETUP
3 - P ROTOCOL SETUP
4-COMM SETUP
5-LIGHT CONTRO L
6-TEMP CONTRO L
T E M P E R ATURE CONTRO L
1-REFR CIRCUIT #1
2-REFR CIRCUIT #2
3-REFR CIRCUIT #3
4-REFR CIRCUIT #4
MORE ON NEXT PAG E
T E M P E R ATURE CONTRO L
1-REFR CIRCUIT #5
2-REFR CIRCUIT #6
3-REFR CIRCUIT #7
4-REFR CIRCUIT #8
MORE ON NEXT PAG E
REFR CIRCUIT #1
TEMP CONTRO L – E N A B L E D
S E T P O I N T – 15 F
R AT E – 3 F
O U T P U T – - 1