Corp. Network Router User Manual
CONFIG MENU (continued)
2- PRESSURE #2
Press 2 on the Keypad to enter the Pressure #2
Submenu.
PRESSURE #2 controls the suction pressure or
Split Suction on the Protocol Control. Press the
C L R k e y. Key in the applicable suction pres-
sure in psig for
H I A L A R M and press E N T.
Repeat for
L O A L A R M.
Pressure Transducers are supplied in one of three
ranges:
0 to 100
0 to 200
0 to 500
Using the key, toggle to the range of the trans-
ducer used. Press ENT.
Using the key, move down to the Alarm status
selection. Using the key, toggle
ENABLED or
DISABLED. Press ENT.
O ffset allows manual calibration for the pressure
t r a n s d u c e r. Manual calibration is achieved by
entering a number between -5 and +5. This number
will then be used to offset the pressure reading by
the entered amount.
WA R N I N G: Impro p e r calibration of the
t r a n s d u c e r could lead to unpre d i c t a b l e
operation of the control. Verify the accu-
racy of the transducer reading with a
minimum of two gauges.
N o t e : Manual calibration is available on Hand
Held version V2.40 or greater.
Press ESC to return to S
E N S O R SE T U P ME N U.
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.) 970307
P/N 374511B
Page 12
PROTOCOL
™
Hand Held Device
PRESSURE #2
HI ALARM 0 PSI
LO ALARM 0 PSI
XDCR RANGE - 100 PSI
ALARM ENABLED
OFFSET 0 PSI
SENSOR SETUP MENU
1-PRESSURE #1
2-PRESSURE #2
3-TEMP #1
4-TEMP #2
5-TEMP #3