Corp. Network Router User Manual

CONFIG MENU (continued)
2- SENSOR SETUP
Press 2 on the Keypad to enter the Sensor Setup
Submenu. This screen has 6 menus.
1- PRESSURE #1
Press 1 on the Keypad to enter the Pressure #1
Submenu.
PRESSURE #1 controls the suction pressure for
the Protocol Control. Press the CLR key. Key in
the applicable suction pressure in psig for
HI
ALARM and press ENT. Repeat for LO ALARM.
Pressure Transducers are supplied in one of three
ranges:
0 to 100
0 to 200
0 to 500
Using the key, toggle to the range of the trans-
ducer used. Press ENT.
O ffset allows manual calibration for the pressure
t r a n s d u c e r. Manual calibration is achieved by
entering a number between -5 and +5. This number
will then be used to offset the pressure reading by
the entered amount.
WA R N I N G: Impro p e r calibration of the
t r a n s d u c e r could lead to unpre d i c t a b l e
operation of the control. Verify the accu-
racy of the transducer reading with a
minimum of two gauges.
N o t e : Manual calibration is available on Hand
Held version V2.40 or greater.
Press ESC to return to S
E N S O R SE T U P ME N U.
970307 HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)
P/N 374511B
Page 11
PROTOCOL
Hand Held Device
PRESSURE #1
HI ALARM 40 PSI
LO ALARM 20 PSI
XDCR RANGE - 100 PSI
OFFSET 0 PSI
CONFIG MENU
1-SET THE CLOCK
2-SENSOR SETUP
3 - P ROTOCOL SETUP
4-COMM SETUP
5-LIGHT CONTRO L
6-TEMP CONTRO L
SENSOR SETUP MENU
1-PRESSURE #1
2-PRESSURE #2
3-TEMP #1
4-TEMP #2
5-TEMP #3