Quick Start Guide

48 hunter.direct/ACC2help
START STATIONS, PROGRAMS, AND BLOCKS
When using Conditional Response to start a station, Block, or
program, other options appear below the selection.
MODE
If the Mode is set to Manual, the station, Block, or program
will run alone, and all other automatic irrigation is stopped
until the response is nished.
If the Mode is set to Auto, the response will occur without
halting other scheduled irrigation. If the system is using
Flow Manager, the response may not begin immediately.
The responding stations will be t into the Flow Target, as
available, by the Flow Manager.
If Stop if Condition Clears is checked, the station, Block, or
program will only run while the trigger condition is present.
If the condition continues, a station or Block will run for
the specied run time, and a program will run once for the
duration of the program.
If the box is not checked, the response will continue for the
total run time or duration of the program.
SWITCH P/MVS
To enable P/MV switching on sensor input, each station in
the aected Flow Zone should be set to call for both P/MV
outputs.
When the sensor is alarmed, or changes position, it should
then be set to “Close P/MV” for the P/MV that is not wanted.
In this way, only 1 P/MV would be active at any given moment,
because the stations are calling for both of them, but one is
disabled by the sensor input.
Example: There are two points of connection available, one
potable water, and one non-potable. Each has its own Master
Valve. A oat switch is installed to monitor the non-potable
level. All stations are set at Station Setup to call for both
Master Valves.
When the oat switch is closed, it disables the P/MV for the
potable water supply, so only non-potable water is used.
When the oat switch is open, it disables the P/MV for the
non-potable supply, so only potable water is used.
They will not both be disabled at the same time, since only
one position can be in eect at a time.
Conditional Response