STATION SETUP
Flow Manager requires:
• The station’s Flow Zone assignment
• The Flow Priority (checked or not checked)
• The station Flow Rate.
FLOW ZONE
This tells the controller which Flow Zone the station belongs
to.
A dierent ow target can be set for each ow zone. The ow
target should be a safe rate of ow (approximately 5 /sec
or 1.5 m/sec) for the diameter of the mainline pipe in the ow
zone.
It is also possible to have Flow Zones that run without Flow
Manager, simultaneously with Flow Zones that are being
managed.
FLOW PRIORITY
The priority setting helps the controller decide which stations
to run sooner to achieve Flow Targets. Stations with the
Priority box checked will be considered rst, so that less
critical stations can occur later in the irrigation.
FLOW RATE
If the system is equipped with a ow sensor, it is best to use
the “Learn Flow” function to let the controller ll these values
in.
If the system does not have a ow sensor, look up or calculate
reasonable ow values for each station, and enter manually
for each station.
Note that Copy and Paste do not work with ow rates. They
only copy the upper half of the screen, including P/MV and
Flow Zone assignments.