Quick Start Guide

38 hunter.direct/ACC2help
Flow Operations
VIEW FLOW
Current ow rate on all sensors can be viewed from the
Home/Activity screen at any time. Press the so key for View
Flow to see actual ow on up to 6 ow sensors.
If the controller is equipped with the optional Wi-Fi module,
the current ow can also be viewed on a mobile device.
FLOW ALARM HANDLING
When stations are running, the Flow Monitor continuously
checks the actual ow from the sensor(s) against the
combined learned ow of the stations, including the overow
and underow percentages allowed in the Flow Zone. It also
checks this ow against the higher level Flow Zone limits, and
MainSafe™ limits if applicable.
If the total amount caused by running stations is exceeded
beyond the permissible station delay periods, the controller
pauses all stations (shutting o the P/MV) in the Flow Zone. It
waits 60 seconds aer the stations are paused, for the ow to
drop to near 0.
If the View Messages so key is active, you must
clear the messages before the View Flow key
appears.