Decodercommfailed:Thismayindicateacompletedecoderfailure,ORthedecodermaynotbeconnectedor
poweredproperly.VerifyALLconnections:ICDHPtoprogrammingcup(bothends)anddecoderpower.Ifthe
decoderisconnectedinthetwowirepathbutthecontrollerpowerisOff,
decoderwillnotrespond.Ifdecoder
andICDHPareconnectedcorrectly,anddecoderhaspower,andDecodercommfailedmessageappears,
decoderislikelydefective.
Current:Displayselectricalcurrentdrawofdecoderinmilliamps.Standbyrangeisapproximately35ma.Whendecoder
isactive,thisvaluewillbehigher,
dependingonnumberandtypeofdevicesconnectedtodecoderoutput.Totalcurrent
onadecodercannotexceed1000ma.
Thecurrentdisplaydoesnotchangeinrealtime.Ifastationisstartedorstopped,runthediagnosticGetDecoderStatus
againtoseethenewcurrentdraw.
Output:The
outputmatrixshowsthestatusofeachoutputofthedecoder.Thedisplaywillshowthenumberofoutputs
forthesizeofdecoderdetected(asinglestationdecoderwillonlyhave1output).
Solenoid:Showswhetherasolenoidorsimilardeviceisdetectedontheoutput(Y=Yes,N=No).
TheSolenoidstatusmaynotchangeuntilpowerhasbeencycledoff/ontothedecoder,ifasolenoidhasjust
beenaddedtothedecoder.Turnoffeitherthecontroller,orremovetheADM99decoderoutputmodulefrom
thecontroller,forapproximately15seconds,andthenturnthepowerbackon
(orreplacetheADM99).Solenoid
statuswillbeupdated.