User's Manual
17
pressed,theICD‐HPwillrefusetosendtheprogramuntiltheduplicatenumbershavebeenchanged.
Theoutputswithduplicatenumberswillflash“Duplicate”,alternatingwiththeoutputnumbers.
Pump:IftheTypewaschangedtoPump(insteadofastationdecoder),onlyOutput1willbeshown.
Use+and–to
changebetweenP/MV‐1andP/MV‐2.(P/MV=Pump/MasterValve).
Programming:Whenallsettingsaremade,andoutputsarenumbered(seeImportantNotessection),presstheNext3
buttontosendthestationnumberstothedecoder.
Thedisplaywillshow“Programming…”fora
shorttime.Ifsuccessful,“ProgrammingComplete”willappearafterthe
programhasbeensent.
Decodercommfailed:Thismessageindicatesthattheprogrammingwasnotsuccessful.Mostlikelycausesarethe
connections,orthedecoderpower.Checkpowerleadstothedecoder,programmingcupcableconnections,andverify
thereis
poweronthetwo‐wirepathfromthecontroller(ifprogramminginline).
TurnLinePowerOff,andBackOn:Afterprogrammingorre‐programminginstalleddecoders,thetwo‐wirepathpower
mustbeturnedofffor15seconds,andthenbackon,fortheprogrammingtotakeeffectin
thefield.
Thestationnumberswillbeinthedecoder’smemory,butthepowermustbecycled(off/on)totakeeffect.Youcanturn
offpowertothecontroller,orremovetheADM99outputmodulefromthecontroller,andthenplugitbackinafter15
seconds.