10271450001 Revision E 512 Installing IFL cables
Hub installation
Follow these steps to ground the lightning arrestor:
1. Connect one end of the ground cable (No. 6 AWG or
greater, green) to the lightning arrestor ground bar, as
shown in figure 5-9.
hb097
To ground
point
Ground cable
No. 6 AWG or greater
Single-hole compression lug
Ground bar
Figure 5-9 Hub lightning arrestor grounding connections
2. Route the ground cable to the ground point.
When routing the ground cable, you must:
Secure the ground cable at 5foot (1.5meter)
intervals.
Keep the ground cable at least 3 feet (0.9 meters)
away from nongrounded metal objects.
Make sure all bends in the cable have a sweeping
radius of more than 8 inches (20.3 centimeters).
3. Connect the hub lightning arrestor to the same ground
(reference) point as the ODU ground. See section 4.11.
4. Apply antioxidant (HNS 90082240002) to each ground
lug.
5. Apply 1/2inch (13millimeter) heat shrink tubing (HNS
90074880005) to each ground lug after the connection is
complete.
Important: You must slip the heat shrink onto the cable
before you make the connections.
Grounding the lightning
arrestor