Cut Sheet
Certificate:
2218736
Master Contract:
151933
Project:
2429874
Date Issued:
July 19, 2011
DQD 507 Rev. 2009-09-01 Page: 2
• Flexible connection fittings, rain-tight, Series EKJ-S*** conduit size 2-1/2 in., with flexible lengths ranging
from 12 to 36 in. Inside radii of bends should not be less than 24 in. for the 2-1/2 in.
Class I, Groups C and D; Class II, Groups E, F and G; Class III:
• Flexible connection fittings, rain-tight, Series EKJ***SS conduit sizes 3 and 4 in. with flexible lengths
ranging from 12 to 36 in. Inside radii of bends should not be less than 36 in. for the 3 in., and 48 in. for the
4 in. EKJ may be followed by UF, may be followed by MF or FF, maybe followed by Ex. EKJ***SS may
have UF prior to the SS, may have MF or FF after the SS may be followed by Ex.
• Flexible connection fittings, rain-tight, Series EKJ-S*** conduit sizes 3 and 4 in., with flexible lengths
ranging from 12 to 36 in. Inside radii of bends should not be less than 36 in. for the 3 in., and 48 in. for the 4
in.
CLASS 4418 83 – CONDUIT FITTING – Fittings for Metal Conduit – For Hazardous Locations – Certified to
US Standards
Class I, Groups A, B, C and D; Class II, Groups E, F and G; Class III:
• Flexible connection fittings, rain-tight, Series EKJ conduit size ½ and ¾ in. and EKJ***SS conduit sizes ½
and ¾ in. with flexible lengths ranging from 4 to 36 in. Inside radii of bends should not be less than 10 in.
for the 1/2 in. and 12 in. for the 3/4 in. Series ECF conduit size 3/4 in. with flexible lengths ranging from 4 to
36 in. Inside radii of bends should not be less than 12 in. for the 3/4 in. EKJ may be followed by UF, may be
followed by MF or FF, maybe followed by Ex. EKJ***SS may have UF prior to the SS, may have MF or FF
after the SS may be followed by Ex.
Class I, Groups C and D; Class II, Groups E, F and G; Class III:
• Flexible connection fittings, rain-tight, Series EKJ and EKJ***SS conduit sizes 1, 1-1/4, 1-1/2 and 2 in. with
flexible lengths ranging from 4 to 36 in. Inside radii of bends should not be less than 14 in. for the 1 and 1-1/4
in. and 16 in. for the 1-1/2 and 2 in. Series ECF conduit size 1 in. with flexible lengths ranging from 4 to
36 in. Inside radii of bend should not be less than 14 in. for the 1 in. EKJ may be followed by UF, may be
followed by MF or FF, maybe followed by Ex. EKJ***SS may have UF prior to the SS, may have MF or FF
after the SS may be followed by Ex.
PART B
PRODUCTS
CLASS 3428 02 - FIXTURES AND FITTINGS-For Hazardous Locations
Class I, Groups A, B, C and D; Class II, Groups E, F and G; Class III:
• Flexible fixture fittings, rain-tight , Series EKJ, conduit sizes 1/2, 3/4 and 1 in. with flexible lengths ranging
from 4 to 36 in. Inside radii of bends should not be less than 10 in. for the 1/2 in., 12 in. for the 3/4 in. and 14
in. for the 1 in EKJ may be followed by UF, may be followed by MF or FF, maybe followed by Ex.
CLASS 3428 82 - FIXTURES AND FITTINGS-For Hazardous Locations-Certified to U.S. Standards
Class I, Groups A, B, C and D; Class II, Groups E, F and G; Class III: