Owner manual

68
LP-294 REV. 2.20.14
BOILER CONFIG
Pump Mode 2
Manifold with CH
DHW and Gen. pump
Pump modes are displayed during selection in 2 lines. Options:
0 - CH and DHW pump
1 - General pump with 3 WV
2 - Manifold with CH Gen and DHW pump
3 - Manifold with Gen pump and 3WV
4 - Manifold with Sys Pump DHW ext
Default is 2.
Table 37 Boiler Config Quick Start-Up
2. CENTRAL HEATING SETTINGS
Return to the Installer Menu by pushing the key. Enter the CH Settings Menu by pushing once, then . To change values, press
ENTER until the value starts blinking. Use the or ▲ keys to change the value. Once the appropriate selection is made, hold the
ENTER button until the value stops blinking to save the selection.
SCREEN
DESCRIPTION
CH SETTINGS
CH mode 1
CH with Thermostat
and Outdoor Reset
The CH Mode is set default to 0 Single Boiler with Room Thermostat and Outdoor Reset, but can
be changed to a value appropriate for the installation. Options:
0 = CH with thermostat
1 = CH with thermostat and outdoor reset
2 = CH outdoor reset and T-night offset (done by a timer) The boiler operates on readings from the
outdoor sensor in this mode.
3 = CH with permanent heat demand The boiler is always operating.
4 = CH with analog input for T-supply (for both single and cascaded boilers) (requires 0-10 V input,
available on optional Interface Module)
5 = CH with analog input for mod-rate (single boiler only) (requires 0-10 V input, available on optional
Interface Module)
6 = CH with hydro-air unit (single boiler only) The boiler does not step modulate in this mode, and
operates with a more aggressive PID.
After selecting the CH Mode, press the ▼ key once to modify the CH Differential.
CH SETTINGS
Central heating
Differential
10
o
F
The CH Differential is the + and bandwidth for the CH Setpoint (the CH Setpoint is accessed in the
User Menu). Options:
(1) - The Differential to the setpoint for starting the boiler can be modified here. Default: 10
o
F. Range:
2 27
o
F.
(2) - For CH-mode 6, the values are different, and depend on set point. The CH mode selected will
determine the default.
Table 38 CH Settings Quick Start-Up
3. DHW SETTINGS
Return to the Installer Menu by pushing the key. Enter the DHW Settings Menu by pushing once, then .
The DHW Mode is set default to 0, or No DHW, but can be changed to a value appropriate for the installation.
Several domestic hot water modes can be selected. To change values, press ENTER until the value starts blinking. Use the or
keys to change the value. Once the appropriate selection is made, hold the ENTER button until the value stops blinking to save the
selection.
SCREEN
DESCRIPTION
DHW SETTINGS
DHW mode 1
Manifold with CH
DHW and Gen. pump
0 - No DHW (only central heating)
1 - DHW store with sensor
2 - DHW store with thermostat
3 - Instant. DHW with FlowSW DHW-T-Sens. (not used)
4 - Instant. DHW with DHW-T-Sens. (not used)
5 - Instant. DHW with DHW-T + FlowSens. (not used)
Once DHW Mode is confirmed, push ▼ to set the DHW-Store Differential.
BOILER SETTINGS
DHW-Store
Differential
_7
o
F
The DHW-Store Differential is the + and differential for the DHW Setpoint (the DHW Setpoint is
accessed in the User Menu).
NOTE: This screen is visible in DHW mode 1 & 2 ONLY.
The differential to the storage tank setpoint can be set here.
The default is 7
o
F. Range: 1 36
o
F.
Once the DHW-Store Differential is set, push the ▼ key to set the CH/DHW Priority.