Manual

GSC53N - GSC57 - ZG47
EN - 89
8.5.2. “METER" mode
In this mode the instrument shows one of the screens below according to the settings
made as per paragraph 8.1.
27.09.00 17:35:12
27.09.00 17:35:12
27.09.00 17:35:12
CURRENT
SINGLE PHASE
I1 = 30.21 A
Ipk1 = 49.53 A
ThdI = 23.06 %
freq = 50.0 Hz
CLAMP TYPE: FlexINT
CURRENT
I1 = 30.21 A
I2 = 23.53 A
I3 = 23.06 A
freq = 50.0 Hz
CLAMP TYPE: FlexINT
CURRENT
I1 = 30.21 A
I2 = 23.53 A
I3 = 23.06 A
IN = 8.4 A
freq = 50.0 Hz
CLAMP TYPE: FlexINT
HARM.
WAVE
PG-
PG+
HARM.
WAVE
PG-
PG+
HARM.
WAVE
PG-
PG+
Example of screen in single-
phase mode
Example of screen in “3 wires”
three-phase mode
Example of screen in “4 wires”
three-phase mode
The symbols used are described in Table 8
For any message displayed see Appendix 1 MESSAGES DISPLAYED.
Following keys are enabled:
F1: to pass to "HARMONIC" mode (see paragraph 8.5.3).
F2: to pass to "WAVE" mode (see paragraph 8.5.4).
F3/F4: to pass to previous/next function respectively.
SAVE: to save in the instrument memory a record of “Smp” type (see
paragraph 9.2) containing the instantaneous values of voltage and
current present on the instrument inputs. This function is disabled
during a recording.
ENTER/HOLD: to enable/disable the HOLD function (updating interruption) of the
displayed data. All the previous functions remain however available.
When the HOLD function is enabled, the word HOLD is displayed.
When this function is enabled it’s not possible to record or take an
energy measurement. This function is disabled during a recording or
an energy measurement.
MENU: to enter in the MENU mode and change the instrument settings (see
paragraph 8.1 and 8.2). It’s not possible to enter the configuration
MENU during a recording or an energy measurement.
START/STOP: to record selected parameters according to the instrument’s settings
(see chapter 10).