Manual

GSC53N - GSC57 - ZG47
EN - 77
1
st
Page of the RECORDER
CONFIG MENU
Example of 2
nd
page in single-
phase mode with ANOM flag
enabled
Example of 2
nd
page in “3
wires” three-phase mode with
ANOM flag enabled
Example of 2
nd
page in “4 wires”
three-phase mode with ANOM
flag enabled
Example of sub-page
"VOLTAGE HARMONICS"
RECORDER CONFIG
START
MANU
STOP
MANU
INT. PERIOD: 15min
HARM REC: ON
ANOM REC: ON
+
-
RECORDER CONFIG
VOLTAGE:
V1
HARM. REC:Pg (ON)
Vref P-N: 230V
LIM+: 06% (243.8V)
LIM-: 10% (207.0V)
+
-
RECORDER CONFIG
VOLTAGE:
V12 V32 V31
HARM. REC:Pg (ON)
Vref P-P: 400V
LIM+: 06% (424.0V)
LIM-: 10% (360.0V)
+
-
RECORDER CONFIG
VOLTAGE:
V1 V2 V3
V12 V32 V31
HARM. REC:Pg (ON)
Vref P-N: 230V
LIM+: 06% (243.8V)
LIM-: 10% (207.0V)
+
-
ENTER
RECORDER CONFIG
VOLTAGE HARMONICS
Thd DC 01 02 03 04
05 06 07 08 09 10 11
12 13 14 15 16 17 18
19 20 21 22 23 24 25
26 27 28 29 30 31 32
33 34 35 36 37 38 39
40 41 42 43 44 45 46
47 48 49
+
-
Use the keys F1, F2 to position the
cursor on the desired word and use
the keys F3 / F4 to modify the
value.
Press ENTER to confirm this page
and proceed inside the Menu
keeping the settings made.
Press ESC to leave this page
without modifying the existing
parameters.
Use the keys F1, F2 to position
the cursor on the desired
voltage harmonic and use the
keys F3 / F4 to select /
deselect (it’s selected if
highlighted in black). Press
ENTER to confirm this page
keeping the settings made.
Press ESC to leave this page
without modifying the existing
parameters.
The instrument will record the
values of the selected
harmonics corresponding to
the voltages selected in one of
the two pages of the Menu
previously illustrated.
ENTER
MENU
To Select MANUAL or AUTOMATIC
start/stop mode, place the cursor on
MANU or AUTO using the key F1 or
F2 and select the desired mode using
F3 or F4.
If you want to change Voltage Harm. Selection place the
cursor on the corresponding “Pg” symbol then Press F3
Use the keys F1, F2 to position the
cursor on the desired word and use
the keys F3 / F4 to select / deselect
the desired parameter (it’s selected
if marked in black).
Press ENTER to confirm this page
and proceed inside the Menu
keeping the settings made.
Press ESC to leave this page
without modifying the existing
parameters.