Manual
GSC53N - GSC57 - ZG47
EN - 66
In the RMIS mode If the
value of the resistance
is over the maximum
measurable, the
instrument emits an
acoustic signal and
displays a screen similar
to displayed to side.
LOW 05.06.01
Resistance value higher
than the maximum
measurable.
>0.999
9.12A
RMEAS RLIM=0.150
Test current
FUNC
The displayed result can be stored pressing the SAVE key twice (according to
paragraph 9.1).
In the VDROP mode If
the value of the voltage
drop is higher than the
limit, the instrument
emits an acoustic signal
and displays a screen
similar to displayed to
side.
LOW 05.06.01
Voltage Drop higher than
the limit.
3.50 V
14.0A 0.350
VDROP SECTION:2.5
Test current
Resistance value
FUNC
The displayed result can be stored pressing the SAVE key twice (according to
paragraph 9.1).
In the VDROP mode If
the value of the voltage
drop across the
conductor under test is
over the maximum
measurable, the
instrument emits an
acoustic signal and
displays a screen similar
to displayed to side.
LOW 05.06.01
Voltage drop over the
maximum measurable.
>9.99V
----A >0.999
VDROP SECTION:2.5
FUNC
The displayed result can be stored pressing the SAVE key twice (according to
paragraph 9.1).