Manual

GSC53N - GSC57 - ZG47
EN - 46
At the end of the test
the instrument emits a
double sound signal
indicating that the test
is correctly
terminated and
displays the values
alongside.
LOOP 05.06.01
Value of phase to Earth
Resistance expressed in .
1.07
215A
Freq=50.0HZ
VP-N=231V Vp-PE=231V
P-PE
Value of the phase to Earth
prospective short circuit
current expressed in Ampere
calculated according to the
following formula.
FUNC
Z2
Working mode
WARNING
Never disconnect the test leads from the circuit under test when the
message " MEASURING " is displayed.
Formula for calculation of prospective short circuit current:
PN
N
CC
Z
U
I
where U
N
= Nominal phase to neutral voltage = 127 if V
meas
150
230 if 150V< V
meas
250
This result can be stored pressing the SAVE key twice (according to paragraph 9.1).