Manual
GSC53N - GSC57 - ZG47
EN - 36
This screen is displayed
when the phase
conductor has been
exchanged with the
Protection Conductors.
The instrument does not
effect the test. Reverse
the phase to earth
connection in the plug or
exchange the black
cable with the green one
RCD 05.06.01
- - - ms
FRQ=50.0Hz Ut= ---V
VP-N= 2V VP-PE= 230V
CHANGE P-PE
x1 30mA 50V
Phase and Protection
Conductors are
exchanged.
FUNC
IdN
RCD
UL
This screen is displayed
when in a 230V Phase
to Phase System the
blue conductor was
reversed with respect to
the green one.
The instrument does not
effect the test. Reverse
the blue and green
conductors.
RCD 05.06.01
- - - ms
FRQ=50.0Hz Ut= ---V
VP-N=130V VP-PE= 227V
CHANGE N-PE
x1 30mA 50V
Neutral and Protection
Conductors are
exchanged.
FUNC
IdN
RCD
UL
If a contact voltage U
t
higher than the
selected limit (U
L
) is
detected, the instrument
interrupts the test and
emits a long sound
signal at the end of the
test and displays the
screen alongside.
RCD 05.06.01
- - - ms
FRQ=50.0Hz Ut= ---V
VP-N=234V VP-PE= 234V
UT DANGEROUS
x1 30mA 50V
The instrument doesn't
detect an efficient
protection circuit.
FUNC
IdN
RCD
UL
If the instrument detects
that the earth cable
(green) is not
connected, the screen
alongside is displayed
for 5 seconds then the
initial display is back.
Check the connections
of PE conductor under
test.
RCD 05.06.01
- - - ms
FRQ =50.0Hz Ut= ---V
VP-N=234V VP-PE= 34V
NO PE
x1 30mA 50V
Message “NO PE”: the
instrument doesn't detect
an efficient protection
circuit.
FUNC
IdN
RCD
UL