Manual

GSC53N - GSC57 - ZG47
EN - 34
6.3.2.5. Results of " R
A
" mode
4. Press the START key once: the instrument carries out the test.
WARNING
Never disconnect the test leads from the circuit under test when the
message " MEASURING " is displayed.
The RCD must NOT
trip and the instrument
emits a double sound
signal indicating the
positive outcome of
the test and displays the
screen alongside.
RCD 05.06.01
Global Earth Resistance
Value).
12
FRQ=50.0Hz Ut= 1V
VP-N=231V VP-PE=231V
Ut OK
RA 30mA 50V
Value of contact voltage U
t
detected referred to the
rated value of the RCD
current set.
OK:Contact Voltage Not
Dangerous.
FUNC
IdN
RCD
UL
Contact Voltage Limit value
Working mode
RCD nominal current
RCD type
5. The test can be stored pressing the SAVE key twice (according to paragraph
9.1).
START
STOP