Manual
GSC53N - GSC57 - ZG47
EN - 18
6.1.3. Results of "AUTO" mode
At the end of the test, if
the average resistance
value Ravg is lower
than 5 the instrument
emits a double sound
signal indicating the
positive outcome of
the test and displays
one screen similar to the
screen alongside.
LOW 05.06.01
Average resistance value
(Ravg)
1.05
R+ R-
1.07 1.03
219mA 219mA
AUTO 0.11
Resistance values and
corresponding test current
got exchanging the
polarities of test leads
FUNC
CAL
The displayed result can be stored pressing the SAVE key twice (according to
paragraph 9.1).
6.1.4. Results of "RT+" and "RT-" modes
if a resistance value
RT+ or RT+ lower than
5 is detected, the
instrument emits a
double sound signal
indicating the positive
outcome of the test
displays one screen
similar to the screen
alongside.
LOW 05.06.01
Max Resistance value of
R+ or R-.
1.07
219mA
RT+ 0.11 TIME: 10s
Test current
Duration of the Test
FUNC
CAL
Note: We recommend to use crocodiles and to check if the crocodiles make a good contact
with the conductor under test. Indeed in this test the instrument gives as final result
the maximum measured value of R+ or R- and suing test leads instead of crocodiles
could give you faulty result due to faulty contact between the test leads and conductor
under test
The displayed result can be stored pressing the SAVE key twice (according to
paragraph 9.1).