Manual

GSC53N - GSC57 - ZG47
EN - 107
4. Press ENTER key. The instrument displays the message Data savedfor a while to
confirm the desired configuration (see above on the right). The instrument return to the
measure mode.
Below you can find the parameters for each of 5 Typical Configurations:
EN50160
ANALYSER CONFIG:
System: not modified
Frequency: not modified
Current Range: not modified
Clamp Type: not modified
TV Ratio: not modified
Password: not modified
RECORDER CONFIG:
Start: MANU
Stop: MANU
Integration period: 10min
Recording of harmonics: ON
Recording of Voltage anomalies (voltage Surge and Dips) : ON
Voltage Reference for Dips and Surge detection: 230V(single, 3ph4w); 400V(3ph3w)
Upper Limit for Dips and Surge detection: 6%
Lower Limit for Dips and Surge detection: 10%
Selected voltages: V1(single); V12,V32,V31(3ph3w); V1,V2,V3 (3ph4w)
Selected voltage harmonics: THD,DC,01,02,03,04,05, … 25 (single,3ph3w);
THD, 01,02,03,04,05,06,07,08,09,10,11,13,15,17,19,21,23,25 (3ph4w)
CO-GENERATION: OFF
SURGES & DIPS
ANALYSER CONFIG:
System: not modified
Frequency: not modified
Current Range: not modified
Clamp Type: not modified
TV Ratio: not modified
Password: not modified
RECORDER CONFIG:
Start: MANU
Stop: MANU
Integration period: 1min
Recording of harmonics: OFF
Recording of Voltage anomalies (voltage Surge and Dips) : ON
Voltage Reference for Dips and Surge detection: 230V(single, 3ph4w); 400V(3ph3w)
Upper Limit for Dips and Surge detection: 6%
Lower Limit for Dips and Surge detection: 10%
Selected voltages: V1(single); V12,V32,V31(3ph3w); V1,V2,V3, V12,V32,V31(3ph4w)
Selected current: I1 (single); I1,I2,I3 (3ph3w, 3ph4w);
CO-GENERATION: OFF