If the user changed the instrument’s settings can quickly resume the above configuration
using the RESET option (see paragraph 5.4).
By pressing START/STOP the recording of the selected parameters is started according to
the settings made in the MENU (see paragraphs 8.1 and 8.2). The rotary switch position
doesn’t affect the recording setting.
As the default value of the integration periods is set at 15 minutes the instrument will store
data in the temporary memory for 15 minutes. Afterwards the instrument will elaborate the
results saved in the temporary memory and will save the result of this elaboration (min,
avg, and max values) in the definitive memory. Therefore, if an integration period of 15
minutes has been set, the recording will continue for about 15 minutes before producing a
series of recorded values. If the recording is interrupted before the selected integration
period has completely elapsed the data stored in the temporary memory will not be
elaborated and the corresponding series of values won’t be transferred to the definitive
memory.
10.2.2. Typical Configurations
To activate the Typical Configurations, follow this procedure:
1. Turn the rotary switch on “ANALYSER”.
2. Press MENU key. The instrument shows the following screen:
MENU GENERAL
SAFETY TEST MEMORY
ANALYSER MEMORY
RESET
ANALYSER CONFIG
RECORDER CONFIG
CONTRAST
DATE&TIME
LANGUAGE
3. Press MENU key again. The instrument displays a screen as shown below (picture on
the left). This way is possible to select the desired configuration with F1 or F2 key.
TYPICAL CONFIG.
EN50160
SURGES & DIPS
HARMONICS
START-UP
POWER & ENERGY
TYPICAL CONFIG.
EN50160
SURGES & DIPS
HARMONICS
START-UP
POWER & ENERGY
Data saved
Configuration selection
Confirmation configuration selection