Manual

GSC53N - GSC57 - ZG47
EN - 105
10.2. SETTING TYPICAL CONFIGURATIONS
In order to facilitate this task, the instrument is provided of the following two pre-setting
recording modes:
1. Default Configuration: it’s comprehensive which should fit most cases.
2. Typical Configuration: it’s possible to select recording with pre-setting parameters for
the following situations:
EN50160
Setting parameters for Networks Quality in compliance with EN 50160
standard (see paragraph 17.11.2).
SURGES & DIPS
Setting parameters for Voltage Anomalies detection (surges, dips, break,
etc.) (see paragraph 17.10).
HARMONICS
Setting parameters for Harmonics Analysis of Voltage and Current (see
paragraph 17.11).
START-UP
Setting parameters for Start-Up motors and electrical devices.
POWER & ENERGY
Setting parameters for Power and Energy measures (see paragraph 17.12).
10.2.1. Default Configuration
The default configuration of instrument consists in the following parameters settings:
ANALYSER CONFIG:
System: 3PH4W
Frequency: 50Hz
Current Range: 1000A
Clamp Type: FlexINT
Transforming ratio of voltmetric transformers: 1
Password: OFF
RECORDER CONFIG:
Start: MANU (the recording is started
1 minute after pressing
the START/STOP key)
Stop: MANU
Integration period: 15min
Recording of harmonics: ON
Recording of Voltage anomalies (voltage Sag and Surge) : ON
Voltage Reference for Sag and Surge detection: 230V
Upper Limit for Sag and Surge detection: 6%
Lower Limit for Sag and Surge detection: 10%
Selected voltages: V1, V2, V3
Selected voltage harmonics: THD, 01, 03, 05, 07
Selected currents: I1, I2, I3, IN
Selected current harmonics: THD, 01, 03, 05, 07
CO-GENERATION: OFF
Powers, Pf and cos selected: Pt, P1, P2, P3
Qti, Q1i, Q2i, Q3i
Qtc, Q1c, Q2c, Q3c
St, S1, S2, S3
Pft, Pf1, Pf2, Pf3
dpft, dpf1, dpf2, dpf3
Energies: Eat, Ea1, Ea2, Ea3
Erit, Eri1, Eri2, Eri3
Erct, Erc1, Erc2, Erc3