b) The active power P of each phase is positive. If negative, turn the clamp of the
phase in question.
c) The value of the Pf of each phase is not excessively low (typically it’s not lower than
0.4). In case the Pf is lower than 0.4, check if the phase voltage is associated to the
right clamp meter (for example the voltage of phase 1 must be associated to the
clamp meter no. 1).
d) After checking, and if needed modifying, the connection of the instrument to the
equipment re-set the 3 wires mode and the connections shown in the picture (blue
and red wire together).
5. Apply voltage to the electrical equipment under test (if previously shut off for the
instrument connection).
6. The values of the available electrical parameters will be displayed of the instrument.
For further details see the paragraph relevant to the position of the switch.
7. You can press HOLD to interrupt the updating in real time of the displayed values.
8. You can press SAVE to save the displayed values (see paragraph 9.2).
9. If you want to record:
a) Check and eventually modify the values of the basic parameters (see paragraphs
8.1 and 8.2).
b) Check and eventually modify the recording parameters by pressing MENU (see the
paragraph corresponding to the position of the rotary switch selected).
c) To start the recording press START (see chapter 10.1).