Owner manual
VEGA78
EN - 24
5.2.4. Single phase system – Screens sequence
12/09/2006 – 16:55:10
PHASE 1 RMS VALUES – Page x/y
V1N
VNPE
Freq
I1
Patt1
Preatt1
Papp1
Pf1
CosPhi1
=
=
=
=
=
=
=
=
=
0.0 V
0.0 V
0.0 Hz
0.0 A
0.0 W
0.0 VAr
0.0 VA
0.00i
0.00i
PAGE SCOPE HARM VECTORS
PARAMETERS CAPTION:
V1N Phase-Neutral voltage L1 phase
VNPE Neutral-Ground voltage
Freq Frequency
I1
Current on L1 phase
Pact1 Active Power L1 phase
Preact1 Reactive Power L1 phase
Papp1 Apparent Power L1 phase
Pf1 Power factor L1 phase
CosPhi1 Power factor between fundamental of
voltage L1 and current L1
Fig. 39: Page of numerical values
25/01/2013 – 16:55:10
TOT. ENERGY CONSUMPTION – Page x/y
Eact = 0 kWh
Ppeak = 0 kW
Date Ppeak : -- / -- / -- 00:00:00
Start rec. : -- / -- / -- 00:00:00
Stop rec. : -- / -- / -- 00:00:00
Rec. Time : - - -
Int. Per. : - - - Rec: - -
PAGE SCOPE HARM VECTORS
PARAMETERS CAPTION:
Eact Total active energy consumed when starting
recording.
Ppeak Maximum peak of consumed active power.
Date Ppeak Date and time in which the peak occurred.
Start rec. Date when recording was started.
Stop rec. Date when recording was stopped.
Rec. Time Time elapsed from Rec Start.
Int. Per. Value of the set integration period.
Rec Number of the recording in progress
Fig. 40: Consumed energy page
CAUTION
The Total Consumed Energy page is shown only if the instrument has been
set for the Recording of the General Parameter Total “Active Power &
Energy” (see § 5.4.6.1). Values will be shown only during or at the end of a
recording and zeroed upon starting a new recording or when the instrument
is switched off
25/01/2013 – 16:55:10
TOT. ENERGY PRODUCTION – Page x/y
Eact = 0 kWh
Ppeak = 0 kW
Date Ppeak : -- / -- / -- 00:00:00
Start rec. : -- / -- / -- 00:00:00
Stop rec. : -- / -- / -- 00:00:00
Rec Time : - - -
Int. Per. : - - - Rec: - -
PAGE SCOPE HARM VECTORS
PARAMETERS CAPTION:
Eact Total active energy produced when starting
recording.
Ppeak Maximum peak of produced active power.
Date Ppeak Date and time in which the peak occurred.
Start rec. Date when recording was started.
Stop rec. Date when recording was stopped.
Rec Time Time elapsed from Rec Start.
Int. Per. Value of the set integration period.
Rec Number of the recording in progress
Fig. 41: Producted energy page
CAUTION
The Total Produced Energy page is shown only if recording parameter “Co-
generation” has been set in the instrument (see § 5.4.5) and if general
parameter Total “Active Power & Energy” has been selected (see § 5.4.6.1).
Values will be shown only during or at the end of a recording and zeroed
upon starting a new recording or when the instrument is switched off.