User guide

400 Series
EN - 65
Tripping current ( )
IdN [mA] Type Range IdN [mA] Resolution [mA] Uncertainty
10
AC
(0.5 1.1) IdN
0.1IdN -0%, +10%rdg
A
(0.3 1.1) IdN
> 10
AC
(0.5 1.1) IdN
A
(0.3 1.1) IdN
RCD type AC ( ), A ( ), general and selective
Tripping time resolution 1ms, uncertainty (2.0%rdg + 2dgt)
Earth resistance (Ra)
Range [] Resolution []
Uncertainty
1 1999
1
(5.0rdg + 3dgt)
RCD type AC ( ), A ( ), general and selective
Test current < ½ IdN, uncertainty: -10%, +0% IdN
Contact voltage Ut range: 0 2Ut lim resolution: 0.1V uncertainty: -0%, +(5%rdg + 3dgt)
Line impedance and fault loop impedance (LOOP)
Phase-neutral and phase-earth voltage range (110 240V) 10%
Phase-phase voltage range (110 415V) 10%
Frequency 50Hz 0.5Hz, 60Hz 0.5Hz
TT and TN systems
Range [] Resolution []
Uncertainty
0.01 9.99
0.01
(5.0rdg + 3dgt)
10.0 199.9
0.1
200 1999 (phase-earth only)
1
Max peak test current at test voltage 3A @ 127V, 6A @ 230V, 10A @ 400V
IT systems
Range [mA] Resolution [mA] Uncertainty
5 999
1
(5.0rdg + 3dgt)
Contact voltage (ULIM) 25V, 50V
Total earth resistance (Ra)
Range [] Resolution []
Uncertainty
0.01 9.99
0.01
(5.0rdg + 1)
10.0 199.9
0.1
200 1999 (phase-earth only)
1
Test current <15mA
Contact voltage (ULIM) 25V, 50V
Phase-neutral and phase-earth voltage range (110 240V) 10%
Frequency 50Hz 0.5Hz, 60Hz 0.5Hz
Phas sequence (123)
Phase-neutral and phase-earth voltage range (110 240V) 10%
Frequency 50Hz 0.5Hz, 60Hz 0.5Hz
Leakage current (LEAK)
Range [mV] Resolution [mV] Uncertainty
1 1200.0
0.1
(1.0rdg + 2dgt)
Max crest factor 3
Response time 10ms
Frequency 50Hz 0.5Hz, 60Hz 0.5Hz