Instruction Manual

I-V400 - SOLAR I-V
EN - 16
5.2.2.2. PV plant parameters
1. Press MENU key, position the cursor onto EFF by using
the arrow keys (,) and confirm with ENTER. The
display shows the screen here to the side, which contains
the global parameters of the system.
15/05/10 15:34:26
PRp - - -
Irr - - - W/m2
Pnom 150.0 kW
Tc - - - °C
Te - - - °C
Pdc - - - kW
Pac - - - kW
ndc - - -
nac - - -
GO – start rec.
Select
MPP
2. Press the ENTER key. The instrument shows the
following options: MPP300 status, Set PV plant. and Set
Instrum.
3. Use the arrow keys (,) to select “Set PV plant” and
confirm with ENTER. The instrument shows the following
screen:
15/05/10 15:34:26
PRp - - -
Irr - - - W/m2
Pnom 0.000 kW
Tc - - - °C
Te - - - °C
Pdc 0.0 kW
Vdc 0.000 V
Idc 0.0 A
ndc - - -
MPP300 status
Set PV plant
Set instrum.
Select
MPP
4. By using the arrow keys ( , ) it is possible to set:
Pmax maximum rated power of PV installation
expressed in kW
Range coefficient of power variation with
temperature, characteristic parameter of PV modules
(typically in range: -0.3 -0.5%/C)
Noct rated operating temperature of the cell,
characteristic parameter of PV modules (typically in
range: 42 48°C)
Te, Tc setting of default values of environmental
and PV module temperatures. These values are taken
into consideration by the instrument only when probe
is not connected to unit SOLAR-02
Corr. Type Setting of the compensation
relationship on the calculation of Pdc power and the
maximization of DC performance (see § 5.2.3)
15/05/10 15:34:26
Pmax
: 3.500 kW
Gamma
: 0.45 %/°C
Noct
: 45 °C
Te
: 40 °C
Tc
: 45 °C
C
orr.T
yp
e.
:
T. Env
SAVE to store data
MPP