Owner manual
SIRIUS89N
EN - 92
EN50160
ANALYZER CONFIG:
All the parameters: unmodified
RECORDER CONFIG:
Start: MANU (the recording starts at
00 sec mark on clock after
pressing the START/STOP key)
Stop: MANU
Integration period: 10min
Recording of harmonics: ON
Recording of Voltage anomalies (voltage Dips and Surge) : ON
Voltage Reference for Dips and Surge detection: 230V
Upper Limit for Dips and Surge detection: 6%
Lower Limit for Dips and Surge detection: 10%
Selected voltages: V1
Selected voltage harmonics: THD, DC, 01, 02, 03, 04, … 25
CO-GENERATION: OFF
SURGES & DIPS
ANALYZER CONFIG:
All the parameters: unmodified
RECORDER CONFIG:
Start: MANU (the recording starts at
00 sec mark on clock after
pressing the START/STOP key)
Stop: MANU
Integration period: 1min
Recording of harmonics: OFF
Recording of Voltage anomalies (voltage Dips and Surge) : ON
Voltage Reference for Dips and Surge detection: 230V
Upper Limit for Dips and Surge detection: 6%
Lower Limit for Dips and Surge detection: 10%
Selected voltages: V1
Selected current: I1
CO-GENERATION: OFF
HARMONICS
ANALYZER CONFIG:
All the parameters: unmodified
RECORDER CONFIG:
Start: MANU (the recording starts at
00 sec mark on clock after
pressing the START/STOP key)
Stop: MANU
Integration period: 10min
Recording of harmonics: ON
Recording of Voltage anomalies (voltage Dips and Surge) : OFF
Selected voltages: V1
Sel. Harmonics voltage : THD,DC,01,03,05,07,09,11,13,15,17,19,21,23,25
Selected current: I1
Sel. Harmonics current: THD,DC,01,03,05,07,09,11,13,15,17,19,21,23,25
CO-GENERATION: OFF