AC Power/Energy – (Vmeas > 200V, Pf=1)
Clamp FS [A] Range [W] [Wh] Resolution [W] [Wh] Accuracy
1< FS 10
0.000k 9.999k
0.001k
(0.7rdg + 3W/Wh)
10.00k 99.99k
0.01k
(0.7rdg+30W/Wh)
10< FS 200
0.00k 99.99k
0.01k
(0.7rdg+30W/Wh)
100.0k 999.9k
0.1k
(0.7rdg+300W/Wh)
200< FS 1000
0.0k 999.9k
0.1k
(0.7rdg+0.3kW/kWh)
1000k 9999k
1k
(0.7rdg+3kW/kWh)
Vmeas = Voltage in which the power is measured
Power factor and Cos
Range Resolution (°) Accuracy (°)
0.20 0.50
0.01
0.6
0.50 0.80
0.7
0.80 1.00
1.0
Voltage and current harmonics
Range Resolution Accuracy
DC 25
th
0.1V / 0.1A
(5.0rdg + 2dgt)
26
th
33
th
(10rdg + 2dgt)
34
th
49
th
(15rdg + 2dgt)
The harmonics will be zeroed under the following conditions
DC: if the value of DC <0.5% of the value of the fundamental or if the DC value < 0.5% of the clamp's full scale
1st harmonic: if the value of the 1st harmonic <0.5% of the clamp's full scale
2nd 49th harmonic: if the value of harmonic <0.5% of the value of the fundamental or if <0.5% of the FS clamp
11.2. REFERENCE GUIDELINES
Safety: IEC/EN 61010-1 + A2(1996)
Insulation: double insulation
Pollution level: 2
Max. height of use: 2000m (6562ft)
Measurement category: CAT IV 300V AC (to ground), Max 460V between inputs
11.3. GENERAL CHARACTERISTICS
Mechanical characteristics:
Dimensions (L x W x H): 245 x 210 x 110mm (10 x 8 x 4in)
Weight: 1.5kg (3lv)
Power supply
Internal power supply: rechargeable Li-ION battery
Battery life: approx. 1 hour
External power supply: Ing. Red-Yellow: 100 415V, 50/60Hz, 20mA
Measurement and memory
Number of samples per period: 128, (64 in “Real Time” connection)
Max. recordable parameters: 383 (simultaneously)
Max. recordable voltage anomalies: 65530
Integration period: 5, 10, 30s, 1, 2, 5, 10, 15, 60min
Recording autonomy: > 30 days (@ IP = 10 minutes)
Memory: 8Mbyte
11.4. ENVIRONMENT
11.4.1. Environmental conditions for use
Reference temperature: 23°C ± 5°C (73°F ± 41°F)
Operating temperature: C ÷ 40 °C (32°F ÷ 104°F)
Allowable relative humidity: <80%HR
Storage temperature: -10°C ÷ 60°C (14°F ÷ 140°F)
Storage humidity: <80%HR
This instrument satisfies the requirements of Low Voltage Directive 2006/95/EEC (LVD) and of EMC
Directive 2004/108/EEC
11.5. ACCESSORIES
See enclosed packing list