Manual
MACROTEST 5035
EN - 27
If the instrument detects that the earth
cable (green) is not connected, the
screen alongside is displayed for 5
seconds then the initial display is back.
Check the connections of PE conductor
under test.
RCD ~
o>1999 Ω
no PE
THE PREVIOUS RESULT CANNOT BE SAVED.
In the tests MAN x1, x2, x5 and AUTO
(during x1 and x5 tests), if the RCD
trips to separate the circuit within a time
not complying with the limits reported in
table, the instrument emits a long
sound signal at the end of the test and
displays the values alongside.
RCD ~
o 487 ms
Ι
∆N
30mA 1 V
x1
MAN
t
0° U
L
= 50V
If the RCD trips within a time higher
than the instrument’s measuring limits,
the instrument emits a long sound
signal at the end of the test and
displays the values alongside.
RCD ~
o> 999 mS
Ι
∆N
30mA 2 V
x1
MAN
t
0° U
L
= 50 V
The maximum duration depends on the test type:
Test type General RCD Selective RCD
MAN x1 test 999ms 999ms
MAN x2 test 200ms 250ms
MAN x5 test 50ms 160ms
“ ” test 300ms
SAVING: The tests can be stored pressing the SAVE key twice
(according to paragraph 5.1).
RCD tripping time
ATTENTION: the
tripping time is
higher than the
standard limit.
RCD tripping
time:
> maximum
measuring time
(it depends on
type of test, see
following table).
Message
“no PE”: the
instrument does
not detect the
protection circuit.