11 TECHNICAL SPECIFICATIONS
The accuracy is calculated as [% rdg + (number of dgt) * resolution] at reference condition
indicated in § 11.2
Step/Contact voltage measurement
Measured voltage range Resolution Accuracy
0.01 19.99mV
0.01mV
(2.0rdg + 2dgt)
20.0 199.9mV
0.1mV
200 1999mV
1mV
2.00 19.99V
0.01V
20.0 59.9V
0.1V
Calculated voltage range Resolution Accuracy
0.0 199.9V
0.1V
calculated value (*)
200 999V
1V
(*) The calculated value of step/contact voltage is obtained by the relationship: U
S
=Umis
·
Iflt/Igen
;
U
C
=Umis
·
Iflt/Igen
;
Fault current range (selectable): 10A 200kA
Input resistance (selectable): 1k, 1M
Noise reducing: DSP 55Hz filtering, 64dB rejection of 50/60Hz noise
Generated current range Resolution Accuracy
0.00 9.99A
0.01A
(3.0rdg + 5dgt)
10.0 99.9A
0.1A
(3.0rdg + 3dgt)
Generated current: 55A max
Test voltage: <55V
Test frequency: 55Hz
Earth resistance measurement
Measurement range Resolution Accuracy
0.001 1.999 0.001
(2.0rdg + 5dgt)
2.00 19.99 0.01
20.0 99.9
0.1
100.0 199.9 (5.0rdg)
Open voltage: < 50V AC
Test current: < 7.5A
Frequency of test signal: 55Hz
Influence of probe resistance: ±(10%rdg + 10dgt)
(Rc, Rp)
max (10 + 100R) or 2k considering lower value
Automatic test of probe resistance: Yes
Automatic detection of voltage noise
Ground resistivity measurement
Measurement range Resolution Accuracy
0.00m 9.99m 0.01m
Calculated value, considering
accuracy of resistance to earth
function
10.0m 99.9m 0.1m
100m 999m 1m
1.00km 9.99km 0.01km
10.0km 99.9km 0.1km
Principle of measure: Wenner method = 2** distance* R