Manual

FULLTEST 3
EN - 85
TRMS Residual voltage (URES)
Display range
Resolution
(V)
Accuracy
(general)
Overvoltage protection
10 460
1 ± (3% rdg. + 3 V) CAT III 300 V
10 650
Input voltage (UTRIG): 0 460 VAC
Nominal mains voltage: 230 or 240 V
Measurement method: 4-wire connection (INTERNAL measurement, 1 s or 5 s)
2-wire connection (PLUG measurement, 1 s)
Residual voltage limit value: 60 V RMS
Input voltage URES:
Display range
(V)
Resolution
(V)
Accuracy
10 460 VAC
1 ± (2% rdg. + 2 V)
10 650 VDC
Input resistance (URES): 100 M
Input voltage UTRIG:
Display range
(V)
Resolution
(V)
Accuracy
10 265 VAC
1 ± (2% rdg. + 2 V)
Input resistance (UTRIG): 450 k